Operating Modes SMA Solar Technology AG
18 SB_SMC-BEN092840 User Manual
3.4.4 The yellow LED blinks twice
Grid fault
The yellow fault LED lights up for 5 seconds when the fault occurs, and then starts emitting the
following blink code. 3 seconds off and then 2 brief consecutive blinks. This code is emitted 3 times
in succession. If this fault is still present, the fault signal starts over again.
With this fault signal the inverter indicates a grid fault which can have the following causes:
Grid undervoltage (voltage drop protection)
Grid overvoltage (voltage rise protection)
Grid underfrequency (frequency decrease protection)
Grid overfrequency (frequency increase protection)
Grid frequency change ("dFac")
Voltage increase protection activated
Faulty grid connections, e.g. N and L swapped or PE not connected
(SMC 9000TL(RP) / 10000TL(RP) / 11000TL(RP): Display message <Check L-N-PE>)
In systems which consist of 3 or more Sunny Mini Centrals, the Power Balancer has detected a
fault.
Correction of error by installer
Contact your installer to have the following points checked:
Check whether there is a general power failure (check function of other energy
consumers).
Check the fuse of the inverter power supply.
Check whether the circuit breaker is switched on.
Check the inverter's grid connection.